iSF6-1800E SF6 Multi Analyzer

iSF6-1800E SF6 Multi Analyzer

Description

iSF6-1800E for measuring dew point, purity, decomposition byproducts and chamber pressure for GIS switchgear and high voltage equipment. It can collect/store used SF6 gas in an on-board cylinder. The used gas can be pumped back to the original equipment under test after analyzing.

Features
Highly precise flow auto control
SF6 zero emission
NDIR for purity measurement
Built-in recovery and pumping system

 

 

Description

iSF6-1800E is designed for measuring dew point, purity, ecomposition products and chamber pressure for GIS switchgear and high voltage switchgear equipment. It can recovery used SF6 gas in an on-board cylinder. The used gas can be pumped back to the original equipment under test after analyzing. iSF6-1800E has integrated advanced measuring cells, i.e. thin-film polymer technology for SF6 dew point measurement, non-dispersed Infrared (NDIR) technology for SF6 purity measurement. The unique way of sampling, high precision flow control and touch screen operation improve the accuracy and ease of use.

 

Features

 

  • Highly precise flow auto control
  • SF6 zero emission
  • NDIR for purity measurement
  • Built-in recovery and pumping system
  • Fast response feasible operation
  • One-key start operation
  • Large capacity data storage
  • Pressure and temperature compensation
  • Self-sealing coupling
  • Multi-language selection
  • TFT true color touch screen
  • Overload protection

 

 

Specifications

Specifications
Moisture content
range: -60 ℃~+30 ℃ (Optional:-80 °C~+20 °C)
humidity content by volume: 11~20,000 ppmv
humidity content by weight: 1.3~2,500 ppmw
accuracy: ≤±2℃ 
ppmv /ppmw: ≤±2ppm+20% of reading
resolution: ±0.01℃

Purity
range: 0~100 %
accuracy: ±0.5 %
accuracy: 0.01 %

Decomposition Products (Optional)
SO2: range: 0~20ppmv
accuracy:≤±2% F.S.
SO2: range: 0~100ppmv
accuracy:≤±2% F.S.
SO2: range: 0~500ppmv
accuracy:≤±2% F.S.
HF: range: 0~10ppmv
accuracy:≤±3% F.S.
H2S: range: 0~100ppmv
accuracy: ≤±3% F.S.
CO: range: 0~1000ppmv
accuracy: ≤±4% F.S.
CF4: range: 0~5000ppmv
accuracy: ≤±2% F.S.
CF4: range: 0~100%
accuracy: ≤±1% F.S.

Pressure:  1~11 bar abs.
Flow rate: 255~600 ml/min
Working condition: 0 ℃~+40 ℃10~90% @40℃, non-condensing
Mains power:  100~240 VAC 50/60 Hz
Dimension:  629 × 497 × 353 mm
Gross weight:  29kg (transport case and accessories included)

Standard Configuration
6m self-sealing stainless steel armoured tube
DN8 self-sealing coupling
DN20 self-sealing coupling
5μm self-sealing rectangular filter
USB storage disk
Power cable
Operation manual
Calibration certificate

Optional accessories
3m self-sealing FEP sampling tube
6m self-sealing FEP Psampling tube
3m self-sealing stainless steel armoured sampling tube
6m self-sealing stainless steel armoured sampling tube

 

Application

Measure dew point, purity, decomposition products of SF6 and pressure for electric equipment filled with SF6 gas.